loeData Center Enterprise and Storage - Todd Turner - 496-8214 / ITIDataCenterManagement@groups.purdue.edu (read further for exceptions for who to call)

File Path: C:\IOC\dcexpert\StruxureWare Data Center Expert 7.8.0\dcexpert

...

Data Center Enterprise and Storage should be notified of any red alarms that appear in StruxureWare by phone call. Yellow alarms should be monitored for changes, but do not need to be reported. FIRE alarms warrants an immediate call. Exceptions to when to call are listed below:

Main Contact: Data Center Enterprise and Storage - Todd Turner - 496-8214 / ITIDataCenterManagement@groups.purdue.edu (read further for exceptions for who to call) If you cannot reach Todd call Patrick Finnegan at 765-427-3020 (Cell), 6-1752 (Office), 765-421-6069 (Home) If you cannot reach  Patrick Finnegan  call Jon Miller 49-67763 (cell 765-414-7646) Phone

...

StruxureWare Alarms that do not require a call (and what to do instead)


Firmware/Software update pop ups

Send e-mail to  ITIDataCenterManagement@groups.purdue.eduAlways ignore these pop-ups. Do not click yes, only close it out or click no.

Communication lost, Connection, or Timeout errors

This alarm means that the server tried to talk to the device and didn’t get a response. Since all of the monitoring is done via the internet there will be times when a communication signal is lost. Please wait for 10 minutes for it to try again. If it still is alarming, contact DCM 496-8214 / ITIDataCenterManagement@groups.purdue.edu.   If ALL devices in a room are down, call right away. Other reasons for a communication loss alarm: the building or room lost power, device lost power, network PIC or cable failure or network switch it is connected to is down.

Humidity Alarms

Whether they are low or high humidity, these alarms in StruxureWare should be reported by email only ITIDataCenterManagement@groups.purdue.edu. Do not call for these alarms.

Dew Point Alarms

These alarms should be reported by email only ITIDataCenterManagement@groups.purdue.edu.

Battery Alarms for UPS devices.

Battery alarms in StruxureWare for UPS devices (devices with "apc" or "trp" in the hostname) should be reported by email only  ITIDataCenterManagement@groups.purdue.edu.

UNLESS!!! The battery alarm is temperature related. Then call. Ex: " internal battery temperature exceeds the critical threshold "

Surveillance Camera

Errors/Test Patterns/Failures

Send email to  ITIDataCenterManagement@groups.purdue.edu

...

Active Alarms will be displayed under the “Active Alarms” tab, and the normal-status green checkmarks next to the devices will change to yellow or red, depending on the nature of the alarm(s).

...

The most important screens within the software to be monitored are the “Device Groups” and “Active Alarms” windows. We are looking for any color other than green , but specifically yellow and/or red in one or both of those windows. Yellow alarms should be monitored for changes, but do not need to be reported.

...