File Path: C:\IOC\dcexpert\StruxureWare Data Center Expert 7.8.0\dcexpert

...

Data Center Enterprise and Storage should be notified of any red alarms that appear in StruxureWare by phone call. Yellow alarms should be monitored for changes, but do not need to be reported (with the exception of door alarms - they should be reported as below, "Routine alarm", and Temperature Alarms (See High Temperature Alarms (red or yellow) or Outage; except 2550 netbotz alarms - see "2550 Netbotz 750 Alarms" below). FIRE alarms warrants an immediate call. Exceptions to when to call are listed below:

...

Routine alarm: Call/Send email once. 

As of 12/17/23,  please note that individual cooling failures that are not causing an overheat condition in the room need only be reported by email message. These are non-critical and will be resolved during business hours.
Ex: crac unit failed (compressor, low or high pressure).

...

Active Alarms will be displayed under the “Active Alarms” tab, and the normal-status green checkmarks next to the devices will change to yellow or red, depending on the nature of the alarm(s).

...

The most important screens within the software to be monitored are the “Device Groups” and “Active Alarms” windows. We are looking for any color other than green , but specifically yellow and/or red in one or both of those windows. Yellow alarms should be monitored for changes, but do not need to be reported (except High Temperature alarms, which should be treated as red alarms).

...